SPOTO's latest exam dumps on the homepage, with a 100% pass rate! SPOTO delivers authentic Cisco CCNA, CCNP study materials, CCIE Lab solutions, PMP, CISA, CISM, AWS, and Palo Alto exam dumps. Our comprehensive study materials are meticulously aligned with the latest exam objectives. With a proven track record, we have enabled thousands of candidates worldwide to pass their IT certifications on their first attempt. Over the past 20+ years, SPOTO has successfully placed numerous IT professionals in Fortune 500 companies.
Take other online exams

Question #1
UPS5000-E (50kVA power module) has a single cabinet capacity of 300kVA and can support 8 racks in parallel.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #2
The total current of the battery pack is 1000A, and 3 sets of batteries are configured. The most economical configuration of the cable from the main switch box to the branch switch box is: ()
A. 95mm^2 (328A) x 2correct
B. 120mm^2 (382A) x 2
C. 150mm^2 (441A) x 2
D. 185mm^2 (506A) X1
View answer
Correct Answer: A
Question #3
What is the total IT load power of the FusionModule1000A V2R3 version 40-foot IT solution?
A. 52kWcorrect
B. 55kW
C. 70kW
D. 72kW
View answer
Correct Answer: A
Question #4
What kind of inlet and outlet wiring methods can the FusionModule2000 integrated power distribution cabinet implement?
A. Inlet and outletcorrect
B. Up-in and down-out
C. Lower inlet and upper outlet
D. Inlet and outlet
View answer
Correct Answer: A
Question #5
Huawei precision air conditioners have RS485 communication interfaces for remote inspection and parameter setting of the system: Modbus open protocol is provided to access the computer room environment monitoring system to reduce service costs.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #6
The water inlet slope of the fan coil condensate tray should be no less than?
A. 0
B. 0
C. 0
D. 0
View answer
Correct Answer: A
Question #7
When a third-party system needs to integrate NetEco or Huawei equipment, Huawei needs to provide northbound interfaces and protocols. The third-party system manufacturer needs to evaluate the access workload and do development and commissioning.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #8
FusionModule2000 integrated UPS has two models: 50K/125K.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #9
The battery type supported by UPS2000-G is ().
A. VRLAcorrect
B. Lithium battery
C. Nickel-cadmium battery
D. Flywheel
View answer
Correct Answer: A
Question #10
The operating temperature range of FusionModule800 is -20~45 degrees, and the operating temperature range of FusionModule500 is 0~45 degrees
A. True
B. Falsecorrect
View answer
Correct Answer: B
Question #11
UPS5000 -A 30~120kVA can support wall installation.
A. True
B. Falsecorrect
View answer
Correct Answer: B
Question #12
The backup time of UPS system is generally within 30 minutes, so it is more reasonable to use constant current method to calculate battery capacity.
A. True
B. Falsecorrect
View answer
Correct Answer: B
Question #13
Three-proof paint coating can significantly reduce the failure rate of UPS in harsh environments such as salt spray, dust, high temperature and humidity, ensuring its service life in harsh environments.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #14
The NetEco management system can provide a temperature cloud map function to monitor the temperature distribution in the computer room and quickly identify hot spots in the computer room.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #15
The NetEco management system can provide a power distribution topology map function, which can realize full-link monitoring of power distribution from the introduction of AC power to the R PDU terminal.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #16
The NetEco management system can automatically calculate the electricity expenses of the computer room based on the tiered electricity price strategy.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #17
Fire extinguishing measures that can be adopted in Class A computer rooms include ()
A. Gas fire extinguishing systemcorrect
B. Water mist fire extinguishing system
C. Automatic sprinkler system
D. All of the above
View answer
Correct Answer: A
Question #18
FusionModule500 & FusionModule800 can be equipped with emergency fans
A. True
B. Falsecorrect
View answer
Correct Answer: B
Question #19
UPS2000-G-(6K-20K) has the strongest lightning protection design in the industry, with lightning protection level (), surge protection level (), which can avoid 90% failure caused by lightning strikes and reliably protect the AC input port of the back-end equipment.
A. 5kA; 6kVcorrect
B. 2kA; 4kV
C. 2kA; 6kV
D. 4kA; 6kV
View answer
Correct Answer: A
Question #20
The power supply modes of FusionModule800 and FusionModule500 are 380/400/415/3Ph/50Hz and 220/230/240/1Ph/50Hz respectively.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #21
Which of the typical configurations of FusionModule800 are optional?
A. Temperature and humidity, door magnet, water immersion, smoke sensor, mobile phone APP
B. Smoke sensor, door sensor, water flooding, SMS alarm, padcorrect
C. Water immersion, door sensor, video, backup power, ibattery
View answer
Correct Answer: B
Question #22
The power module efficiency of UPS5000-E (25-75kVA) is 96%.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #23
The PDU8000 precision power distribution cabinet uses a 7-inch liquid color touch screen, which can graphically display the power distribution cabinet system diagram and the status of each switch.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #24
FusionModule1000A V2R3 version IT solution comes standard with cabinet spring damping device
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #25
The basic principles of refrigeration for air-cooled and water-cooled air conditioners are the same
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #26
The FusionModule2000 sensor uses PoE ring network power supply to improve the reliability of control system signal transmission and can be used to control standards.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #27
The EC fan brand used in the NetCol5000-A025H half-cabinet row-level variable-frequency air-cooled precision air-conditioning indoor unit is Xerox Bai.
A. True
B. Falsecorrect
View answer
Correct Answer: B
Question #28
FusionModule1000A V2R3 version can be customized with bulletproof shell
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #29
The NetEco management system supports reporting alarm information to third-party management systems through the SNMP interface.
A. Truecorrect
B. False
View answer
Correct Answer: A
Question #30
In UPS5000-A system, which of the following battery configuration is unreasonable?
A. 32 12V batteries
B. 37 12V batteriescorrect
C. 40 12V batteries
D. 42 12V batteries
View answer
Correct Answer: B