السؤال #1
Backup time of battery depends on discharge current of battery.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #2
In operant conditioning, the subject is free to make responses at any time, So conditioning is measured by the rate of responding. In most other Ways, however, their forms of learning are essentially the same.
A. When UPSs are connected in parallel, connect loads to the pL terminal
B. When a single UPS works and loads are of the same importance, connect all loads to the sL terminal
C. When a single UPS works and loads are divided into two levels, connect the primary load to the sL terminal and the secondary load to the pl_ terminal
D. When the UPS is overloaded, the loads connected to the sL terminal will be powered off first to ensure continuous power supply to the loads connected to the pj_ terminal
عرض الإجابة
اجابة صحيحة: D
السؤال #3
A certain distance should be reserved at the rear and top of the UPS5000-E, ensuring ventilation and heat dissipation.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #4
During filling refrigerant for NetCol5000-A, there is no need to put the refrigerant steel cylinder upside down on balance.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: B
السؤال #5
If multiple data centers need to be monitored at the same time hierarchical deployment is available.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #6
The principle of the () humidifier is that the high-intensity infrared lamp causes the water surface to release water vapor and diffuse into the air stream that needs to be humidified.
A. igh pressure fogging
B. et film
C. lectrode
D. nfrared
عرض الإجابة
اجابة صحيحة: D
السؤال #7
First time powering on UPS5000-E, make sure that the UPS main input switch, bypass switch, output switch, maintenance bypass switch and battery switch are all OFF
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #8
Which of the following statements is true about UPS5000 power modules and bypass modules?
A. The UPSS000-E-200K and UPS5000-E-400K use the same power module and provide the same capacity of 50 kVA but have different numbers of power modules
B. For UPSs of the same model but in different power segments, their bypass module capacity is the same
C. The power module capacity of both the UPS5000-S and UPS5000-E is 50 kVA
D. The power modules used in the UPSS000-S-1200K are the same as those used in the UPS5000-E- 200K
عرض الإجابة
اجابة صحيحة: A
السؤال #9
Which of the following statements is true about UPS5000 power modules and bypass modules?
A. The UPSS000 - E - 200K and UPS5000 - E - 400K use the same power module and provide the same capacity of 50 kVA but have different numbers of power modules
B. For UPSs of the same model but in different power segments, their bypass module capacity is the same
C. The power module capacity of both the UPS5000 - S and UPS5000 - E is 50 kVA
D. The power modules used in the UPSS000 - S - 1200K are the same as those used in the UPS5000 - E - 200K
عرض الإجابة
اجابة صحيحة: A
السؤال #10
Which air supply mode requires reasonable raised floor height?
A. Air supply mode using blast caps
B. Underfloor air supply mode
C. Air supply mode using wind pipe
D. In-row horizontal air supply mode
عرض الإجابة
اجابة صحيحة: B
السؤال #11
Unpredictable business, expansion and difficult investment is one of the challenges facing the development of traditional data center business.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #12
The UPS5000 option temperature and humidity sensor does not support cascading
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: B
السؤال #13
(___________________) is the signal processing and centralized management module of UPS5000-E
A. Energy control module (ECM)
B. Power Module
C. Bypass Module
D. Maintenance bypass module
عرض الإجابة
اجابة صحيحة: A
السؤال #14
For NetCol5000-A installation, the required time of preserving positive pressure is ( ) hours.
A. 8
B. 12
C. 24
D. 16
عرض الإجابة
اجابة صحيحة: C
السؤال #15
UPS5000-A has built-in SNMP and ModBus card to reduce the management investment cost of customers.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: A
السؤال #16
If IP21 components is configured, the top air outlet kits can also be installed on the UPS5000-E.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: B
السؤال #17
After installing a top air outlet component for the UPS5000, need to set enabled for the top air outlet component on LCD
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #18
For NetCol5000-A installation, the required time of preserving positive pressure is ( ) hours.
A. 8
B. 12
C. 24
D. 16
عرض الإجابة
اجابة صحيحة: C
السؤال #19
Fusion Module2000 is an outdoor prefabricated integrated data center solution.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: B
السؤال #20
The refrigerant air cylinder of Huawei air-cooled air conditioner does not need to be inverted on the electronic scale when charging the refrigerant.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: B
السؤال #21
Which type of report can be exported on the NetEco.
A. Hourly report
B. Daily report
C. Weekly report
D. Monthly report
عرض الإجابة
اجابة صحيحة: ABCD
السؤال #22
If the rotation function of the teamwork is enabled, the active and the standby air conditioners can work alternatively to prolong their service life.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #23
The straight pipe interval fixedly supported by NetCol5000-C piping is (___________________)
A. 3200mm
B. 3000mm
C. 2800mm
D. 2500mm
عرض الإجابة
اجابة صحيحة: D
السؤال #24
First time powering on UPS5000-E, make sure that the load switch is OFF
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #25
A certain distance should be reserved at the rear and top of the UPS5000-E, ensuring ventilation and heat dissipation.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #26
NetCol5000-Acompressor discharge high pressure alarm occurs, it may not that (___________________).
A. The outdoor fan fails to start
B. The outdoor fan is running at low speed
C. The refrigerant is overfilled
D. The refrigerant is insufficient
عرض الإجابة
اجابة صحيحة: D
السؤال #27
Which air supply mode requires reasonable raised floor height?
A. Air supply mode using blast caps
B. Underfloor air supply mode
C. Air supply mode using wind pipe
D. In-row horizontal air supply mode
عرض الإجابة
اجابة صحيحة: B
السؤال #28
If IP21 components is configured, the top air outlet kits can also be installed on the UPS5000-E.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: B
السؤال #29
Which of the following options is a natural cooling system?
A. ater-cooled cold air conditioning system
B. irect ventilation air conditioning system
C. ater-cooled cold water air conditioning system
D. ir-cooled direct expansion air conditioning system
عرض الإجابة
اجابة صحيحة: B
السؤال #30
For NetCol5000-A installation, the required time of preserving positive pressure is ( ) hours.
A. 8
B. 12
C. 24
D. 16
عرض الإجابة
اجابة صحيحة: C
السؤال #31
What is the input/output voltage range of the SmartLi BCU?
A. 280415 V
B. 300400 V
C. 300480 V
D. W00-544 V
عرض الإجابة
اجابة صحيحة: C
السؤال #32
NetEco can mail reports to customers.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #33
In operant conditioning, the subject is free to make responses at any time, So conditioning is measured by the rate of responding. In most other Ways, however, their forms of learning are essentially the same.
A. When UPSs are connected in parallel, connect loads to the pL terminal
B. When a single UPS works and loads are of the same importance, connect all loads to the sL terminal
C. When a single UPS works and loads are divided into two levels, connect the primary load to the sL terminal and the secondary load to the pl_ terminal
D. When the UPS is overloaded, the loads connected to the sL terminal will be powered off first to ensure continuous power supply to the loads connected to the pj_ terminal
عرض الإجابة
اجابة صحيحة: D
السؤال #34
The battery discharge time of UPS2000-G-(6-20kVA) is far less than the design time. The possible cause is that (___________________).
A. Batteries are not fully charge
B. The battery capacity declines
C. The load increases
D. There is no mains input
عرض الإجابة
اجابة صحيحة: ABC
السؤال #35
Temperature cloud map intelligence displayed in NetEco.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: A
السؤال #36
The rated voltage of a cell is
A. 12V
B. 6V
C. 2V
D. 1V
عرض الإجابة
اجابة صحيحة: C
السؤال #37
The refrigerant air cylinder of the Huawei air-cooled air conditioner does not need to be inverted on the electronic scale when charging the refrigerant.
A. ALSE
B. RUE
عرض الإجابة
اجابة صحيحة: A
السؤال #38
First time powering on UPS5000-E, make sure that the load switch is OFF
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #39
For NetCol5000-A installation, the required time of preserving positive pressure is ( ) hours.
A. 8
B. 12
C. 24
D. 16
عرض الإجابة
اجابة صحيحة: C
السؤال #40
The ECC800-Pro is the core component for FusionModule2000 local management. Southbound components can be using the PoE bus.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: A
السؤال #41
FusionModule1000 is an indoor intelligent micro-module data center solution.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: B
السؤال #42
First time powering on UPS5000-E, make sure that the load switch is OFF
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #43
The output terminals of the UPS2000-G-6/10/15/20K include sL and pL. Which of the following statements about the terminals is false?
A. hen UPSs are connected in parallel, connect loads to the pL terminal
B. hen a single UPS works and loads are of the same importance, connect all loads to the sL terminal
C. hen a single UPS works and loads are divided into two levels, connect the primary load to the sL terminal and the secondary load to the pL terminal
D. hen the UPS is overloaded, the loads connected to the sL terminal will be powered off first to ensure continuous power supply to the loads connected to the pL terminal
عرض الإجابة
اجابة صحيحة: D
السؤال #44
When installing the power line on the UPS5000-E, if there are different sources on the main-lines and bypass, you need to remove the copper bars connected to the bypass and main lines first, and then connect the main circuit and bypass input respectively.
A. TRUE
B. FALSE
عرض الإجابة
اجابة صحيحة: A
السؤال #45
If the battery charge current limit coefficient of the UPS5000-E is set to 0.1C10, which of thefollowing statements about this parameter is true?
A. he maximum batten/ charge current is 0
B. he batten/ charge current is always 0
C. he battery float charge current is 0
D. he maximum battery charge current is 0
عرض الإجابة
اجابة صحيحة: A
السؤال #46
Which is not included in the routine maintenance of the ECC800 module?
A. Check whether the power indicator is normal
B. Check the fans for the ECC800 module
C. Check whether the power cable is properly connected
D. Create a micro-module view
عرض الإجابة
اجابة صحيحة: D
السؤال #47
You cannot search for an alarm by setting a filter condition on NetEco's Current Alarms page.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: B
السؤال #48
Commissioning NetCol5000-C drainage devices, after lifting the high float for 5 seconds, two water pumps start working, and the drain abnormal alarm is generated.
A. rue
B. alse
عرض الإجابة
اجابة صحيحة: A
السؤال #49
For NetCol5000-A installation, the required time of preserving positive pressure is ( ) hours.
A. 8
B. 12
C. 24
D. 16
عرض الإجابة
اجابة صحيحة: C
السؤال #50
Which of the following statements is true about UPS5000 power modules and bypass modules?
A. The UPSS000-E-200K and UPS5000-E-400K use the same power module and provide the same capacity of 50 kVA but have different numbers of power modules
B. For UPSs of the same model but in different power segments, their bypass module capacity is the same
C. The power module capacity of both the UPS5000-S and UPS5000-E is 50 kVA
D. The power modules used in the UPSS000-S-1200K are the same as those used in the UPS5000-E- 200K
عرض الإجابة
اجابة صحيحة: A